Delta Electronics — 11.4.2.2. Connecting the DeviceNet Communication Connector

AS Series Module Manual 11 11.4.2 Installation 11.4.2.1. Connecting AS01DNET-A Module to AS series PLC For the details on how AS01DNET-A (in Master/slave mode) is connected to AS series PLC, refer to Section 1.3.1 Installing a Module in AS Series Module Manual. 11.4.2.2. Connecting the DeviceNet Communication Connector  Make sure that the color marks for the PINs of the DeviceNet connection port match the colors of the connection cables and the cable should be connected to the right PIN.  Delta’s power module is recommended as the power module in the communication. 11-14 Input/output Table The scanner module provides an input table of total size:

190 bytes and an output table of total size: 190 bytes for data exchange with slaves. When one slave is configured to the scan list, the configuration software will automatically assign corresponding size of I/O data exchange area to the slave. Input Table and Output Table are the interface for data exchange between the PLC of the master and slaves and show the mapping relationships between the D registers in the PLC of the master and the I/O data of slaves. After the configuration is finished, download the configuration data to the scanner module. Then the module will exchange I/O data with corresponding slaves according to the configuration.

The data in the output table will be transmitted to slaves and the data returned from slaves will be filled in the input table.