AS Series Module Manual When AS01DNET is at different positions of the right of the PLC, the input and output mapping areas for the AS01DNET module in AS PLC are listed in the following table. 11 11.4.3.2. Tables of Input Mapping and Output Mapping areas When AS01DNET works in master mode, the input and output mapping areas for AS01DNET at different positions of the right of AS PLC are listed in the following table.
11-16 Position of Output mapping area Input mapping area AS01DNET on the right of the PLC 1 D26100 – D26199 D26000 – D26099 2 D26500 – D26599 D26400 – D26499 3 D26900 – D26999 D26800 – D26899 4 D27300 – D27399 D27200 – D27299 Position of Output mapping area (for sending data to Input mapping area (for receiving data from AS01DNET the slave) the slave) on the right Data Mapping area Data D register Mapping area D register of the PLC size size 1 D26100~D26103 Bit-strobe command area 4 words D26000~D26003 Scan-list node status indication area 4 words D26104 Reserved 1word D26004 Module status indication area 1 word D26105~D26199 DeviceNet output data area 95 words D26005~D26099 DeviceNet input data area 95 words 2 D26500~D26503 Bit-strobe command area 4 words D26400~D26403 Scan-list node status indication area 4 words D26504 Reserved 1word D26404 Module status indication area 1 word D26505~D26599 DeviceNet output data area 95 words D26405~D26499 DeviceNet input data area 95 words 3 D26900~D26903 Bit-strobe command area 4 words D26800~D26803 Scan-list node status indication area 4 words D26904 Reserved 1word D26804 Module status indication area 1 word D26905~D26999 DeviceNet output data area 95 words D26805~D26899 DeviceNet input data area 95 words 4 D27300~D27303 Bit-strobe command area 4 words D27200~D27203 Scan-list node status indication area 4 words D27304 Reserved 1word D27204 Module status indication area 1 word D27305~D27399 DeviceNet 95 D27205~D27299 DeviceNet input 95