Delta Electronics — 13.4.2 Using AH Series CPU or Non-Delta Master PLC as Upper Device

AS Series Module Manual There are three communication modes for AS00SCM-A plus AS-FCOPM. _13 13.4.2 Using AH Series CPU or Non-Delta Master PLC as Upper Device As CANopen master, AH series CPU need be used together with AH10COPM-5A module to communicate with the CANopen slave AS00SCM-A. See the application situation as illustrated in the following figure. Import IODD file Connect to USB port o r Ethernet port o f AS Series CPU IO - Link Sensor Software: : HWCONFIG4 0 . CANopen Builder Actuator Hub / ….. ….. 16x DI DO / Sensor IO - Link Hub / CAN IO-Link Binary Ethernet / USB Pin2 DI function 13-18 Work mode Description AS Special Remote Mode The AS04SIL-A module is a NIO module.

The number of configurable modules is limited to AS series CPU including remote modules. 4 NIO modules can be configured at most. All SIL modules and IO-Link devices can be configured in HWCONFIG 4.0. and can be monitored online by the software. Delta Special Driver & AS Remote Mode CANopen DS301 Mode Here AS CPU is a CANopen master and AS00SCM-A is a CANopen slave. Up to 4 SIL modules can be configured on the right side of the slave AS00SCM-A (RTU). As many as 64 slaves can be connected to the AS CPU. CANopen Builder does not support the configuration of extension modules on the right side of AS00SCM-A and connected IO-Link devices.

First make the connection in AS special remote mode, complete the configuration of all extension modules and IO-Link devices in HWCONFIG 4.0 and then switch the mode back to CANopen DS301 mode. Open CANopen Builder and configure PDO mapping according to the EDS file of AS00SCM-A with V2.06 or later. For details on operation, see section 13.4.5. ator