Chapter 14 High Speed Counter Module AS02HC Example 2: Encoder with Status Data MSB LSB data Data Length (bits): 28 Multi-Turn Data Length (bits): 12 Multi-Turn Data Start Bit: b27 Single-Turn Data Length (bits): 13 Single-Turn Data Start Bit: b15 Status Data Length (bits): 3 Status Data Start Bit: b2 Parity Check: No check Multi-turn data Status Single-turn data Example 3: Encoder with Parity Check MSB LSB 14 Parity Data Length (bits): 18 Multi-Turn Data Length (bits): 0 Single-Turn Data Length (bits): 17 Single-Turn Data Start Bit: b17 Status Data Length (bits): 0 Parity Check: Even parity check Parity Check Bit: b0 Parity Check Start Bit: b17 Parity Check Length (bits):
17 Single-turn data 4. Monoflop Time The Monoflop Time parameter determines the interval time between two SSI data frames. The correct position data can be received as long as the setting value is greater than that specified for the connected encoder. The range is set as follows. Monoflop CLK DATA 14-15 b27 b26 b25 b24 b23 b22 b21 b20 b19 b18 b17 b16 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b17 b16 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Time MSB LSB Time MSB Parameter Setting Unit Default Monoflop time 4 ~ 2500 16us 4