Delta Electronics — 14.2.6 SSI Input Counting

AS Series Module Manual 5. Maximum Variation Limit The parameter is used to prevent sudden errors occurring in reading absolute position values due to noise interference. You can set the limit value for the variation between two consecutive SSI positions. When the position change exceeds the set limit, the read position value is discarded, the present count value is not refreshed and the error code is displayed in the counter status. When the position change is back within the set range, the counting returns to normal and the error code is cleared. When the maximum position variation limit is set to 0, the function is disabled and no check on the position change will be done. 6.

Absolute Position When the Absolute Position option is selected as the counter type, the counter value will show the absolute position of the SSI absolute encoder within the range of 0 to 2 resolution . The data information including single-turn data, multi- setting of the SSI absolute encoder can be modified as well. Refer to DHCCNT instruction for more. turn data status, data and counting direction can be displayed independently based on the set data format. The offset 7.

Ring Counter 14 When Ring Counter is chosen as the counter type, AS02HC-A is used as a 32-bit ring counter by making two read absolute position variations added up and the count value is changing cyclically in the range of -2147483648 to 2147483647. The counting value changes cyclically within the range of -2147483648 to 2147483647. The ring counter counter value. Refer to DHCCNT instruction for details. value can be cleared to zero through phase Z. The DHCCNT instruction can also be used to clear and preset the 8. Zero Crossing Detection The SSI Zero Crossing Detect function is enabled on the Alarm Setting tab page of the HWCONFIG software.

The alarm will appear if the absolute position of the SSI encoder crosses the zero position. The detection function can be used for both the absolute position and ring counters. The timing for the zero crossing is illustrated in the following table. 14-16 Parameter Setting Unit Default Maximum Variation Limit 0 ~ 2147483647 - 0 (Disabled) Absolute Position 2Res olution 2Res olution Zero Zero crossing crossing Counter value counting up counting down 0 0 The absolute position of SSI encoder (original data) The absolute position of SSI encoder (after offsetting) Zero crossing counting down