Operation Mode ASDA-B3 There are many applications for both absolute type and incremental type registers. You can easily complete a periodic motor operation according to the table above. For example, assume 6 the Position command PR#1 is 10 turns and PR#2 is 20 turns. PR#1 is issued first and PR#2 comes second. The following diagrams show the difference between absolute and incremental positioning. Absolute type Incremental type 20 turns 20 turns 10 turns 10 turns 6.2.3 Control structure of Position mode The basic control structure is shown in the following flowchart.
Position command Position command processing unit Speed loop Position control Current loop Motor unit For better control, the pulse signals are processed by the Position command processing unit. The structure is shown in the following diagram. Position command processing unit GNUM0, GNUM1 Command selection CN1 POS0 - POS6 CTRG Command source Acc. / Dec.
time Delay time Target speed S-curve filter P1.001 P6.000 ︱ P7.099 P5.020 ︱ P5.035 P5.040 ︱ P5.055 P5.060 ︱ P5.075 1 st numerator (P1.044) 2 nd numerator (P2.060) 3 rd numerator (P2.061) 4 th numerator (P2.062) P1.036 Moving filter P1.068 Low-pass filter pulse command External Counter Pulse type selection Denominator (P1.045) P1.008 Inhibit P1.000 Low-frequency vibration suppression P1.025, P1.026 Low-frequency vibration suppression P1.027, P1.028 6-6