Parameters ASDA-B3 YX: control mode setting 8 PT: Position control mode; the command source is from the external pulse and the external analog voltage (coming soon). PR: Position control mode; the command source is from the 100 sets of internal registers which you can select with DI.POS0 - DI.POS6. Multiple homing methods are also available. S: Speed control mode; the command source is from the external analog voltage and the internal registers which you can select with DI.SPD0 and DI.SPD1. T: Torque control mode; the command source is from the external analog voltage and the internal registers which you can select with DI.TCM0 and DI.TCM1. Sz:
Speed control mode; the speed command is zero or the command source is from the internal speed registers which you can select with DI.SPD0 and DI.SPD1. Tz: Torque control mode; the torque command is zero or the command source is from the internal torque registers which you can select with DI.TCM0 and DI.TCM1. Dual mode: you can switch between two modes with external DI. For example, you can use DI.S-P to switch the dual mode of PT/S (control mode setting: 06). Refer to Table 8.1 for further information. Multi-mode: you can switch between three modes with external DI. For example, you can use DI.S-P and DI.PT-PR to switch the multi-mode of PT/PR/S (control mode setting: 0E).
Refer to Table 8.1 for further information. Communication mode: the command source is from the external fieldbus controller, which sends the command to the servo drive through direct communication. 8-32 Mode PT PR S T Sz Tz 00 ▲ 01 ▲ 02 ▲ 03 ▲ 04 ▲ 05 ▲ Dual mode 06 ▲ ▲ 07 ▲ ▲ 08 ▲ ▲ 09 ▲ ▲ 0A ▲ ▲ Communication mode for Delta PLC DVP-15MC and DVP-50MC 0B series models, DMCNET mode 0C CANopen mode, EtherCAT mode Multi-mode 0D ▲ ▲ 0E ▲ ▲ ▲ 0F ▲ ▲ ▲