Delta Electronics — P1.xxx Basic parameters

ASDA-B3 Parameters 8 Settings: Y U X Z  X: additional function for Capture Bit Settings: receiving the DI captured signal within this range once the data is captured. The DI captured signal When the Capture function is enabled and set to capture multiple points (P5.038 > 1), the system stops received within this range is not recognized as valid. Use this function to avoid the system seeing noise as effective signals within the non-capture range. After capturing this mark, activate the masking area. 8-39 Address: 0126H P1.019 Additional function for Capture 0127H Default: 0x0000 Control mode: All Unit: - Setting range: 0x0000 - 0x0101 Format: HEX Data size:

16-bit X Additional function for Capture Z Reserved Y Reserved U Reserved 3 2 1 0 Bit Function Description Bit 0 Cycle mode 0: disable this function. When the number of capturing times (P5.038) is 0, capturing is complete. 1: enable this function. When the number of capturing times (P5.038) is 0, it automatically resets the number of capturing times to the default setting. Bit 1 - Bit 3 Reserved - Address: 0128H P1.020 Capture - masking range 0129H Default: 0 Control mode: All Unit: Pulse unit of capture source Setting range: 0 to +100000000 Format: DEC Data size: 32-bit P1.020 masking pulse number P1.020 masking pulse number Maski ng area P1.021 Reserved