Delta Electronics — P1.xxx Basic parameters

Parameters ASDA-B3 Setting the parameter value when connecting the regenerative resistor with different methods: 8 Settings: In Position (PT) mode, when the deviation pulse number is smaller than the range set by P1.054, DO.TPOS is on. In Position Register (PR) mode, when the deviation between the target position and the actual motor position is smaller than the range set by P1.054, DO.TPOS is on. Example: For a rotary motor, if P1.054 = 167772 and the deviation is less than 167,772 pulses, which equals 0.01 turns (167772 / 16777216 = 0.01), then DO.TPOS is on. Settings: Sets the maximum speed of the servo motor.

8-52 External regenerative resistor Setting External regenerative resistor P 1 kW, 10Ω C Setting: P1.052 = 10 (Ω) P1.053 = 1000 (W) External regenerative resistor (in series) P 1 kW, 10Ω 1 kW, 10Ω C Setting: P1.052 = 20 (Ω) P1.053 = 2000 (W) External regenerative resistor (in parallel) P 1 kW, 10Ω 1 kW, 10Ω C Setting: P1.052 = 5 (Ω) P1.053 = 2000 (W) Address: 016CH P1.054 Pulse range for position reached 016DH Default: 167772 Control mode: PT / PR Unit: pulse Setting range: 0 - 1000000 Format: DEC Data size: 32-bit Address: 016EH P1.055 Maximum speed limit 016FH Default: Rated speed Control mode: All Unit: rpm Setting range: 0 to maximum speed Format: DEC Data size: 16-bit