ASDA-B3 Parameters 8 Settings: When the value is 0 - 100 and the servo motor continuously outputs load that is higher than the setting of P1.056, the pre-warning signal for overload (DO code: 0x10, OLW) is on. If the value is over 100, this function is disabled. Settings: Sets the protection level. For the percentage of rated torque, set the value to 0 to disable the function and set the value to 1 or above to enable the function. Settings: Sets the protection time: when the motor reaches the protection level and the protection time is exceeded, AL030 occurs. Note: this function is only suitable for non-contactable uses, such as electrical discharge machines (set P1.037 correctly). Settings:
0: disable this function. 8-53 Address: 0170H P1.056 Motor output overload warning level 0171H Default: 120 Control mode: All Unit: % Setting range: 0 - 120 Format: DEC Data size: 16-bit Address: 0172H P1.057 Motor hard stop (torque percentage) 0173H Default: 0 Control mode: All Unit: % Setting range: 0 - 300 Format: DEC Data size: 16-bit Address: 0174H P1.058 Motor hard stop (protection time) 0175H Default: 1 Control mode: All Unit: ms Setting range: 1 - 1000 Format: DEC Data size: 16-bit P1.059 Speed command - moving filter Address: 0176H 0177H Operation Panel / software Communication S Control mode: interface: Default: 0.0 0 Data size: 16-bit Unit: 1 ms 0.1 ms - - Format:
One decimal DEC - - Setting range: 0.0 - 4.0 0 - 40 - - Example: 1.5 = 1.5 ms 15 = 1.5 ms - -