Delta Electronics — P1.xxx Basic parameters

Parameters ASDA-B3 8 Settings: The smooth constant of analog Position command is only effective to analog Position command. Settings: Rotation number setting when the maximum voltage (10V) is input to the analog Position command. If the setting on the panel is 3.0 and the external voltage input is +10V, then the Position command is +3 cycles. If the input is +5V, then the Position command is +1.5 cycles. If the input is -10V, then the Position command is -3 cycles. Position control command = Input voltage x Set value / 10 Settings: 0: disable this function. The moving filter smooths the beginning and end of the step command, but it also delays the command. 8-56 Address:

0182H P1.065 Smooth constant of analog Position command 0183H Default: 1 Control mode: Unit: 10 ms Setting range: Format: DEC Data size: Address: 0184H P1.066 Maximum rotation number of analog Position command 0185H Operation Panel / software Communication PT Control mode: interface: Default: 0.0 0 Data size: 16-bit Unit: 1 cycle 0.1 cycle - - Format: One decimal DEC - - Setting range: 0.0 - 200.0 0 - 2000 - - Example: 1.5 = 1.5 cycles 15 = 1.5 cycles - - P1.067 Reserved Address: 0188H P1.068 Position command - moving filter 0189H Default: 4 Control mode: PT / PR Unit: ms Setting range: 0 - 100 Format: DEC Data size: 16-bit