Parameters ASDA-B3 8 Settings: Refer to the description of P1.040. Settings: 0: disable this function. Settings: When the absolute value of the analog input voltage is higher than this set parameter for more than 50 ms, AL042 occurs. The comparison value for this parameter is the original analog input voltage which has not been changed by an offset value through P4.022 (analog speed input offset). Settings: This setting is only for the torque homing mode. As shown in the following figure, after homing is triggered, the motor runs in one direction and reaches the protector. The servo drive then outputs a larger motor current in order to counter the external force.
The servo drive uses P1.087 and P1.088 as the conditions for homing. Since the hard stops are not always the same, it is recommended to return 8-58 P 1.077 - Reserved P 1.080 Second set of maximum rotation speed for analog Speed Address: 01A2H P1.081 command 01A3H Default: Rated speed Control mode: S / T Unit: rpm Setting range: 0 - 50000 Format: DEC Data size: 32-bit Address: 01A4H P1.082 Filter switching time between P1.040 and P1.081 01A5H Default: 0 Control mode: S / T Unit: ms Setting range: 0 - 1000 (0: disable this function) Format: DEC Data size: 16-bit Address: 01A6H P1.083 Abnormal analog input voltage level 01A7H Default: 0 Control mode: S Unit: mV Setting range: 0 - 12000 (0:
disable this function) Format: DEC Data size: 16-bit P 1.084 - Reserved P 1.086 Address: 01AEH P1.087 Torque homing - torque level detection 01AFH Default: 1 Control mode: PR Unit: % Setting range: 1 - 300 Format: DEC Data size: 16-bit