Parameters ASDA-B3 Example: 1. Set P2.094 = 0x11 to enable the first set. 8 2. Set P2.094 = 0x12 to enable the second set. 3. Set P2.094 = 0x13 to enable the first and second sets simultaneously. Settings: Resonance frequency for the first set of low frequency vibration elimination. Settings: Attenuation rate for the first set of low frequency vibration elimination. Settings: Anti-resonance frequency for the second set of low frequency vibration elimination. The setting method is the same as the first set of vibration elimination (P1.089). Settings: Resonance frequency for the second set of low frequency vibration elimination. 8-60 Address:
01B4H P1.090 First set of vibration elimination - resonance frequency 01B5H Default: 4000 Control mode: PT / PR Unit: 0.1 Hz Setting range: 10 - 4000 Format: DEC Data size: 16-bit Address: 01B6H P1.091 First set of vibration elimination - resonance difference 01B7H Default: 10 Control mode: PT / PR Unit: 0.1 dB Setting range: 10 - 4000 Format: DEC Data size: 16-bit Second set of vibration elimination - anti-resonance Address: 01B8H P1.092 frequency 01B9H Default: 4000 Control mode: PT / PR Unit: 0.1 Hz Setting range: 10 - 4000 Format: DEC Data size: 16-bit Address: 01BAH P1.093 Second set of vibration elimination - resonance frequency 01BBH Default: 4000 Control mode: PT / PR Unit:
0.1 Hz Setting range: 10 - 4000 Format: DEC Data size: 16-bit