Delta Electronics — P2.xxx Extension parameters

Parameters ASDA-B3 8 Settings: Special parameter write-in function: Settings: When environmental interference is high, increasing this value can enhance the control stability. If you set the value too high, it affects the response time. Settings: YX Z U  YX: input function selection Refer to Table 8.1.  Z: input contact: A or B contact 0: set this input contact to be normally closed (B contact) 1: set this input contact to be normally open (A contact) Note that you can use P3.006 to determine the source of the digital signal, which can be either an external terminal block or the communication parameter P4.007. 8-66 Address: 0210H P2.008■ Special parameter write-in function 0211H Default:

0 Control mode: All Unit: - Setting range: 0 - 501 Format: DEC Data size: 16-bit Code Function 10 Reset all parameters (cycle the power after reset). 20 P4.010 is writable. 22 P4.011 - P4.021 are writable. 30, 35 Save Capture data. 406 Enable forced DO mode. 400 When forced DO mode is enabled, switch back to the normal DO mode. Address: 0212H P2.009 DI response filter time 0213H Default: 2 Control mode: All Unit: ms Setting range: 0 - 20 Format: DEC Data size: 16-bit Address: 0214H P2.010 DI1 functional planning 0215H 0x0101 (B3-L) 0x0100 (B3-F, E, M) All Default: Control mode: - 0x0000 - 0x015F (last two codes are DI codes) Unit: Setting range: Format: HEX Data size:

16-bit YX Input function selection Z Input contact: A or B contact - - U Reserved