Parameters ASDA-B3 8 Settings: High bit Low bit B C D A Y Z U X X: following error compensation switch (functions under the condition of P1.036 > 1) 0: disable following error compensation 1: enable following error compensation Z: DI.STP triggering method 0: DI.STP is rising-edge triggered 1: DI.STP is level triggered Settings: Y Z U X X: operation mode setting 0: incremental type. An absolute type motor can be operated as an incremental type motor. 1: absolute type. This setting is only applicable to an absolute type motor. If it is used for an incremental type motor, AL069 occurs. Y: pulse command setting when absolute position is lost 0:
when AL060 or AL06A occurs, the system cannot accept a pulse command. 1: when AL060 or AL06A occurs, the system can accept a pulse command. 8-86 Address: 0288H P2.068 Following error compensation switch 0289H Default: 0 x00000000 Control mode: All Unit: - Setting range: 0x00000000 - 0x00000101 Format: H EX Data size: 32-bit A Reserved X Following error compensation switch B Reserved Y Reserved C Reserved Z DI.STP triggering method D Reserved U Reserved Address: 028AH P2.069● Absolute encoder 028BH Default: 0 x0000 Control mode: All Unit: - Setting range: 0x0000 - 0x0111 Format: H EX Data size:
16-bit X Operation mode setting Z Index coordinates function setting when overflow occurs Y Pulse command setting when absolute position is lost U Reserved