Parameters ASDA-B3 initial lead into account. Target value = 400 + 10 x T. For example, if T = 5, the target value is 450. 8 U: if the deviation between the SYNC arrival time and the target value is smaller than the range, it means the synchronization is successful (unit: 10 μs). Settings: Communication protocol is divided into U, Z, Y, and X (hexadecimal): X: reserved. Y: motor status when communication error occurs. 0: motor keeps operating when communication error (AL170) occurs (only applicable in DMCNET mode and CANopen B). 1: motor switches to Servo Off status when communication error (AL180) occurs. Z: source for torque limit (only applicable in DMCNET mode). 0:
communication commands are the source for the torque limit. 1: DI commands are the source for the torque limit. U: PDO alarm is cleared automatically or not 0: if PDO error (AL121 - AL132) occurs, the PDO alarm must be cleared by DI.ARST, NMT: reset node, or 0x6040 fault reset. 1: if PDO error (AL121 - AL132) disappears, the alarm is automatically cleared. Settings: Y Z U X 8-96 Address: 0314H P3.010 CANopen / DMCNET protocol 0315H Default: 0x1010 Control mode: CANopen / DMCNET Unit: - Setting range: 0x0000 - 0xFFFF Format: HEX Data size:
16-bit Digit U Z Y X Function PDO alarm is cleared automatically or not Source for torque limit Motor status when communication error occurs - Range 0 - 1 0 - 1 0 - 1 - Address: 0316H P3.011 CANopen / DMCNET options 0317H Default: 0x0000 Control mode: CANopen / DMCNET Unit: - Setting range: Shown as follows Format: HEX Data size: 16-bit