Parameters ASDA-B3 bit 06: corresponds to DO code = 0x36 bit 14: corresponds to DO code = 0x3E If you set P2.018 to 0x0130, then the output of DO#1 is the bit 00 status of P4.006, and so forth. bit 07: corresponds to DO code = 0x37 bit 15: corresponds to DO code = 0x3F 8 Set the DO codes (0x30 - 0x3F) through communication DO, and then write to P4.006. Settings: The source of the DI input signal can be the external terminal (DI1 - DI5) or the software (SDI1 - SDI5 corresponding to Bit 0 - 4 of P4.007), which is determined by P3.006. If the corresponding bit of P3.006 is 1, which means the source is the software SDI (P4.007); if the corresponding bit is 0, then the source is the hardware DI.
See the following figure: External DI: DI1 - DI5 P3.006 Software DI: SDI1 - DI after combination SDI5 (P4.007 bit) Read parameters: shows the DI status after combining external DI and software DI. Write parameters: writes the software SDI status. This function is the same whether using the panel or communication to set the parameter. For example: if the read value of P4.007 is 0x0011, it means DI1 and DI5 are on; if the written value of P4.007 is 0x0011, it means the software SDI1 and SDI5 are on. Refer to P2.010 - P2.014 for more information on digital input pins (DI1 - DI5). Settings:
Use this communication parameter to read and check if the five keys (MODE, UP, DOWN, SHIFT, and SET) can function normally. 8-102 Address: 040EH P4.007■ Multi-function for digital input 040FH Default: 0x0000 Control mode: All Unit: - Setting range: 0x0000 - 0x3FFF Format: HEX Data size: 16-bit Address: 0410H P4.008★ Input status of servo drive panel (read-only) 0411H Default: - Control mode: All Unit: - Setting range: Read-only Format: HEX Data size: 16-bit