Delta Electronics — P5.xxx Motion control parameters

ASDA-B3 Parameters 8 Settings: The second speed setting for low speed homing. Settings: Set P5.007 to 0 to start homing. Set P5.007 to 1 - 99 to execute the specified PR procedure, which is the same as using DI.CTRG+POSn. You cannot set P5.007 to 100 - 999 as the value exceeds the valid range. Example: to trigger PR#2 Write 1000 to execute stop command, which is the same as DI.STP. When reading P5.007, if the command is incomplete, the drive reads the current command (1 - 99). If the command is complete but DO.TPOS is off (motor position not reached), the drive reads the current command +10000.

If the command is complete and DO.TPOS is on (motor position reached), the drive reads the current command +20000. Commands triggered by DI are also applicable. Example: If the value read is 3, it means PR#3 is in execution but incomplete. If the value read is 10003, it means PR#3 completed, but the motor has not reached the target position yet. If the value read is 20003, it means PR#3 completed and the motor reached the target position. 8-109 Address: 050CH P5.006 Low speed homing (second speed setting) 050DH Operation Panel / software Communication PR (set with P5.004) Control mode: interface: Default: 20.0 200 Data size: 32-bit Unit: 1 rpm 0.1 rpm - - Setting range:

0.1 - 500.0 1 - 5000 - - Format: DEC DEC - - Example: 1.5 = 1.5 rpm 15 = 1.5 rpm - - Address: 050EH P5.007■ Trigger Position command (PR mode only) 050FH Default: 0 Control mode: PR Unit: - Setting range: 0 - 1000 Format: DEC Data size: 16-bit Method 1 Trigger by DI: Register Position command selection 1 - 99 Bit 1 (DI: 0x12) + Trigger command (DI: 0x08) Method 2 Trigger by P5.007: Set P5.007 to 2 to start executing PR#2