ASDA-B3 Absolute System 10.3 System initialization and operating procedures 10.3.1 System initialization After the servo system resumes operation, the controller can acquire the motor’s current 10 absolute position either with communication (such as RS-485) or DI/DO. Delta’s absolute system provides two types of position value for the controller: pulse and PUU. AL06A occurs when you initialize the absolute system for the first time because the coordinate system has not been established. Clear the alarm by setting up the coordinate system. When insufficient battery power or interruption of battery power causes loss of the coordinate system, AL060 occurs.
In the absolute system, when the number of motor rotations exceeds the range - 32768 to 32767, AL062 occurs. When the PUU position value goes outside the range -2147483648 to 2147483647, AL289 occurs. Except for the alarms mentioned above, you can use P2.070 to set up Delta’s absolute servo system. You can choose not to show AL062 and AL289 if the absolute coordinate system overflows when the number of rotations exceeds the range -32768 to 32767 or when the PUU exceeds the range -2147483648 to 2147483647. For example, you might do this on a system that uses incremental commands to operate in a single direction. P2.070 setting: 1. Establish the absolute origin coordinates.
When the coordinate setting is complete, AL06A (or AL060) is automatically cleared. There are two representations to establish the controller's absolute origin coordinates: pulse number and PUU number. You can establish the absolute origin coordinates with DI/DO, parameters, or the PR homing function. 2. When the system is powered on again, the controller can access the motor’s absolute position either with DI/DO or the communication function. Based on the setting of P2.070, the controller can select the requested value, either the PUU (refer to Section 10.3.3) or the pulse value of 16777216, within a single turn (refer to Section 10.3.2). 10-13