Delta Electronics — 11.4.3.1 OD 1XXXh communication object group

ASDA-B3 CANopen Mode Object function: The Life Guarding Protocol includes OD 100Ch and 100Dh. OD 100Ch is the guard time in milliseconds and OD 100Dh is the multiplying factor. Therefore, OD 100Ch multiplied by 11 OD 100Dh gives the life time for the Life Guarding Protocol. If the time (OD 100Ch) is set to 0, then this setting is invalid. Example: if OD 100Ch = 5 ms and OD 100Dh = 10, then life time equals 50 ms. Object 1010h: Store parameters Object function: Write 0x65766173 (save) to sub-index 1 to write all current OD values to the EEPROM. Object 1011h:

Restore parameters 11-37 Index 1010h Name Store parameters Object code ARRAY Data type UNSIGNED32 Access RW PDO mapping No Sub-index 0 Description Number of sub-index Data type UNSIGNED8 Access RO PDO mapping No Setting range UNSIGNED8 Default 1 Sub-index 1 Description Store communication parameters Data type UNSIGNED32 Access RW PDO mapping No Setting range No Default 1 Index 1011h Name Restore parameters Object code ARRAY Data type UNSIGNED32 Access RW PDO mapping No