CANopen Mode ASDA-B3 The state transition is defined as follows: 11 State changes can be achieved with control commands. The commands are as follows: 11-52 Transition Event Action 0, 1 Automatic transition after power-on Device boot and initialization 2 Command shutdown N/A 3 Command switch on Servo is ready for servo on 4 Command enable operation Servo on and executes motion mode 5 Command disable voltage Servo off 6 Command shutdown N/A 7 Command disable voltage or command quick stop N/A 8 Command shutdown Servo off 9 Command disable voltage Servo off 10 Command disable voltage or command quick stop N/A 11 Command quick stop The following two errors belong to this quick stop type: 1.
Trigger positive / negative limit switch 2. Quick stop triggered by a control command (OD 6040h = xxxx x0xxx) Quick stop function is enabled 12 Command Disable Voltage (OD 6040h: 0000 0110 or xxxx xx0x) Servo off 13, 14 Alarm occurs Servo off 15 Alarm is cleared N/A 16 Command enable operation and no alarm Motion operation restart. The restart action is mode-dependent. Setting value Bit of OD 6040h State change Bit 7 Bit 3 Bit 2 Bit 1 Bit 0 Shutdown 0 X 1 1 0 2, 6, 8 Switch on 0 0 1 1 1 3 Switch on + 0 1 1 1 1 3 + 4 Enable operation Disable voltage 0 X X 0 X 7, 9, 10, 12 Quick stop 0 X 0 1 X 7, 10, 11 Disable operation 0 0 1 1 1 5 Enable operation 0 1 1 1 1 4, 16 Fault reset X X X X 15