ASDA-B3 Troubleshooting 12 12-11 AL009 Excessive deviation of Position command Trigger condition and cause 5. Improper setting for the E-Gear ratio. 6. The power cables are loose. Checking method and corrective action 1. Check the value of the maximum deviation (P2.035 Excessive deviation of Position command warning). If the value is too low, set a higher value. 2. Check if the gain value is appropriate for the application. 3. Check if the torque limit setting is appropriate for the application. 4. Check the external load. Reduce the external load or re-evaluate the motor capacity if necessary. 5. Check if the settings for P1.044 and P1.045 are appropriate for the application.
If not, set them to proper values. 6. Check if the power cables are loose. How to clear the alarm? DI.ARST AL010 Voltage error during regeneration Trigger condition and cause Condition: an error occurs during regeneration. Cause: 1. Incorrect selection of the regenerative resistor or no connection to an external regenerative resistor. The regenerative voltage remains at 400V for a period of time during regeneration. 2. P1.053 (Regenerative resistor capacity) is not set to 0 when the regenerative resistor is not connected. Checking method and corrective action 1.
Check the connection for the regenerative resistor, re-calculate the value for the regenerative resistor, and reset the values of P1.052 and P1.053. If the issue persists, send your servo drive back to Delta. 2. Set P1.053 to 0 if not using a regenerative resistor. How to clear the alarm? DI.ARST AL011 Encoder error Trigger condition and cause Condition: the encoder produces abnormal pulses. Cause: 1. Encoder wiring is incorrect. 2. Encoder connector is loose. 3. Encoder wiring is poor.