Delta Electronics — 12.2 Causes and corrective actions

Troubleshooting ASDA-B3 12 12-12 AL011 Encoder error Trigger condition and cause 4. Connection to the encoder is cut off due to interference. 5. Encoder is damaged. Checking method and corrective action 1. Check if the wiring follows the instructions in the user manual. If not, connect the wiring correctly. 2. Check the connection between CN2 and encoder connector. If the connector is loose, reconnect it to CN2. 3. Check if the encoder connector is connected to the motor and CN2 of the servo drive. If there is any poor wiring or damaged wires, replace the connector and cable. 4. Check the communication error rate by setting P0.002 to -80.

If the value continuously increases, it means there is interference. Check the following: (a) Check if the motor is properly grounded. Make sure the power cable (green end) is grounded to the servo drive heat sink. (b) Check if the connection for the encoder signal cable is normal. Make sure the encoder signal cable is separated from the power supply or any high-current cables to avoid interference. (c) Use shielded cable for the encoder. 5. If you took all corrective actions but the issue persists, replace the motor. How to clear the alarm? Cycle power on the servo drive. AL012 Adjustment error Trigger condition and cause Condition:

the calibration value exceeds the allowable value during electronic calibration. Cause: 1. The analog input contact is not correctly returned to zero. 2. The detection device is damaged. Checking method and corrective action 1. Check if the voltage level at the analog input contact is the same as the ground voltage. 2. Reset the power supply. If the issue persists, send your servo drive back to the distributor or contact Delta. How to clear the alarm? Remove the connection cable for CN1 and then execute auto calibration.