Troubleshooting ASDA-B3 12 12-20 AL034 Encoder internal communication error Trigger condition and cause Condition: 1. Internal communication error for the absolute encoder. 2. Internal error for other types of encoder. Cause: encoder internal communication error. Checking method and corrective action 1. Check if the battery wiring is correct or loose. If it is loose, wire it again and cycle power on the system. 2. Check if the battery voltage is within the normal range. 3. Internal communication error for the absolute encoder occurs. Replace the motor. How to clear the alarm? Cycle power on the servo drive.
AL035 Encoder temperature exceeds the protective range Trigger condition and cause Condition: encoder temperature is over the upper limit of 100°C (212°F). Cause: encoder temperature is over 100°C. Checking method and corrective action Set P0.002 to -124 to read the temperature and check if it is below 100°C. If the encoder temperature is higher than 100°C, improve the heat dissipation to lower the temperature. If the temperature difference between the encoder and motor is over 30°C (86°F), send the servo motor back to Delta. How to clear the alarm? After the temperature detector shows a temperature below 100°C, cycle power on the servo drive.
AL042 Analog input voltage is too high Trigger condition and cause Analog input voltage for the Speed command is higher than the level specified by P1.083. Checking method and corrective action Check and make sure the voltage source for the Speed command is correct. Check the value of P1.083 and set it to 0 when this function is not required. How to clear the alarm? DI.ARST