Troubleshooting ASDA-B3 12 12-24 AL062 Number of turns for the absolute encoder overflows Trigger condition and cause Condition: the number of turns for the absolute motor exceeds the range of -32768 to +32767. Cause: motor’s rotation cycle exceeds the allowable range. Checking method and corrective action Check if the motor’s number of turns during operation is within the range between -32768 and +32767. If not, re-execute the homing procedure. How to clear the alarm? Cycle power on the servo drive. AL067 Encoder temperature warning Trigger condition and cause Condition:
the encoder temperature is over the warning level of 85°C (185°F), but still under 100°C (212°F), which is within the protective range. Cause: encoder temperature warning (85°C to 100°C). Checking method and corrective action Set P0.002 to -124 to read the encoder temperature and check if it matches the motor temperature. If the encoder temperature is too high, improve the heat dissipation or decrease the operating temperature. If the temperature difference between the encoder and motor is over 30°C (86°F), send the motor back to Delta. How to clear the alarm? Cycle power on the servo drive. AL068 Absolute data transmitted by I/O is in error Trigger condition and cause Condition:
the time sequence is wrong when you read the absolute position with DI/O. Cause: 1. Time sequence is wrong. 2. Reading timeout. Checking method and corrective action 1. Correct the time sequence for reading the data with DI/O: (a) DI.ABSQ switches to off after DO.ABSR is off. (b) DI.ABSQ switches to on after DO.ABSR is on. 2. Check the duration from when DO.ABSR switches on to the time that DI.ABSQ switches on and see if this duration is over 200 ms. The correct procedure should be: when DO.ABSR switches on and after the bit data of absolute position is ready, read DO.ABSD within 200 ms, switch DI.ABSQ on, and then inform the servo drive that data reading is complete. How to clear the alarm?
Cycle power on the servo drive.