ASDA-B3 Troubleshooting 12 12-25 AL069 Wrong motor type Trigger condition and cause Incremental motor does not support the absolute function. Checking method and corrective action 1. Check whether your servo motor has an incremental or absolute encoder. 2. Check the setting of P2.069 and correctly set the value. Set P2.069.X to 0 if desiring to operate the absolute motor as an incremental motor. How to clear the alarm? Set P2.069.X to 0 and then cycle power on the servo drive. AL06A Absolute position is lost Trigger condition and cause There are two conditions that may cause the loss of absolute position.
One is that the absolute coordinates are not established, so after homing is complete, the origin will not be lost after power cycling. The other is that an error occurred. After homing is complete, AL06A still occurs after power cycling. Coordinates are not established. Condition: 1. Servo drive in use for the first time. 2. The battery is drained and the power supply of the servo drive is cut off. Cause: 1. Servo drive is in use for the first time, so the absolute coordinate system has not been established. 2.
Retaining the absolute position requires power supply, so when the battery is drained and the power supply of the servo drive is cut off, the absolute position of the servo is lost. 3. After the E-Gear ratio is modified, the communication type coordinate system needs to be re-established. An error occurred. Condition: 1. Encoder cable is damaged (including the exterior and the internal wiring). 2. There is a momentary power failure in the battery power supply. 3. The absolute motor is in error. 4. The battery box is used, and J1 and J2 are connected reversely. Cause: 1. Power supply is unstable due to damage of the encoder cable. 2.
The reason for the momentary power failure may be that the battery box connector is loose or excessive machine vibration.