Troubleshooting ASDA-B3 12 12-28 AL075 Encoder absolute number of turns is in error Trigger condition and cause The absolute number of turns in the encoder is in error. Checking method and corrective action 1. Check if the motor is properly grounded. Make sure the power cable is grounded to the servo drive heat sink. 2. Make sure the encoder signal cable is separated from the power supply or any high-current cables to avoid interference. 3. Use shielded cable for the encoder, pull out the shielded mesh, and ground it. 4. Check the motor speed and make sure it is within the rated range. If the issue persists, send your servo motor back to the distributor or contact Delta.
How to clear the alarm? Cycle power on the servo drive. AL077 Encoder internal error Trigger condition and cause Encoder internal error (internal computing error). Checking method and corrective action 1. Check if the motor is properly grounded. Make sure the power cable is grounded to the servo drive heat sink. 2. Make sure the encoder signal cable is separated from the power supply or any high-current cables to avoid interference. 3. Use shielded cable for the encoder, pull out the shielded mesh, and ground it. 4. Check the motor speed and make sure it is within the rated range. If the issue persists, send your servo motor back to the distributor or contact Delta. How to clear the alarm?
Cycle power on the servo drive. AL079 Encoder parameter error Trigger condition and cause The servo drive is not cycled after the parameter is written to the encoder, so the parameter value is not updated. Checking method and corrective action Check if the parameter is written to the encoder. If so, cycle the servo drive to update the parameter. How to clear the alarm? Cycle power on the servo drive.