ASDA-B3 Troubleshooting 12 12-29 AL07B Encoder memory busy Trigger condition and cause Encoder memory is busy. Checking method and corrective action 1. Check if the motor is properly grounded. Make sure the power cable is grounded to the servo drive heat sink. 2. Make sure the encoder signal cable is separated from the power supply or any high-current cables to avoid interference. 3. Use shielded cable for the encoder, pull out the shielded mesh, and ground it. 4. Check the motor speed and make sure it is within the rated range. If the issue persists, send your servo motor back to the distributor or contact Delta. How to clear the alarm? Cycle power on the servo drive.
AL07C Command to clear the absolute position is issued when the motor speed is over 200 rpm Trigger condition and cause The command to clear the absolute position is issued when the motor speed is over 200 rpm. Checking method and corrective action 1. Check if a command to clear the absolute position is issued while the motor speed is over 200 rpm. If so, follow the procedure for clearing the absolute position to clear this alarm. 2. Do not issue a command to clear the absolute position when the motor speed is over 200 rpm. How to clear the alarm? Cycle power on the servo drive.
AL07D Motor stops operating when servo drive power is cycled before AL07C is cleared Trigger condition and cause AL07C occurs and is not cleared before power is cycled on the servo drive, and the motor stops operating. Checking method and corrective action Use DI.ARST to clear the alarm. Once this alarm is cleared, AL07C occurs. Follow the checking and troubleshooting methods to clear that alarm. How to clear the alarm? Cycle power on the servo drive.