Troubleshooting ASDA-B3 12 12-30 AL07E Encoder clearing procedure error Trigger condition and cause The number of times for the encoder to clear the procedure error exceeds 11 times. Checking method and corrective action If the issue persists, set P0.002 to -80 to check the communication quality with the encoder. If the communication is normal, use DI.ARST to clear this alarm. How to clear the alarm? Cycle power on the servo drive. AL07F Encoder version error Trigger condition and cause The encoder version read by the servo drive is in error. Checking method and corrective action N/A How to clear the alarm? Replace the motor immediately.
AL083 Servo drive outputs excessive current Trigger condition and cause Condition: during general operation, this alarm occurs when the servo drive outputs current that is over the allowable level specified by the firmware. This alarm protects IGBT from overheating or burning because of the high current. Cause: 1. UVW cable is short-circuited. 2. Motor wiring is in error. 3. The analog signal GND for the servo drive is interfered. Checking method and corrective action 1. Check the connection between the motor power cable and its connector. If metal wire is exposed or the wire is torn, the UVW cable can short circuit.
In this case, replace the power cable and prevent the metal conductor from being exposed. 2. Refer to Chapter 3 Wiring and check the following: (a) If you do not use the Delta standard power cable, make sure the UVW wiring sequence is correct. (b) Make sure the UVW wiring between the servo drive and motor is correctly connected. 3. Check if the analog signal GND is mistakenly connected to another ground signal (incorrect connection can cause interference). Do not use a common ground for the analog signal GND and other signal cables. Follow the wiring instructions in Chapter 3. How to clear the alarm? Cycle power on the servo drive.