Delta Electronics — 12.2 Causes and corrective actions

Troubleshooting ASDA-B3 12 12-40 AL217 Write parameters: parameter locked Trigger condition and cause Condition: when you use the PR procedure to write parameters, the parameter is write-protected when the servo drive is on or the parameter’s value exceeds the range. Cause: an error occurs when you write parameters with PR#8 command. Checking method and corrective action Write the parameters when the servo drive is off and make sure the parameter’s value is within the range. How to clear the alarm? Modify the PR command and the parameter. AL231 Monitoring item of PR#8 is out of range Trigger condition and cause Condition: the code of the monitoring item for PR#8 is out of range. Cause:

the code of the monitoring item is out of range. Checking method and corrective action Write parameter using PR procedure: when the code of the monitoring item exceeds the range, check the code setting for the monitoring item. How to clear the alarm? DI.ARST AL235 Position counter overflow warning Trigger condition and cause Condition: execute a positioning command after the position command counter overflows. Cause: position command counter overflows. Checking method and corrective action Incremental system: When the motor keeps operating in one direction, this leads to overflow of the position feedback register (FB PUU), and the coordinate system cannot display _ the correct position.

Executing a positioning command after overflow results in this error. Use the scope to check if the feedback position has overflowed and then execute the homing procedure. Absolute system: This error occurs when the absolute positioning command is issued in the following situations: 1. Position feedback register (FB PUU) overflows. _ 2. Absolute origin coordinates are not established after you change the setting of P1.001.Z. 3. Absolute origin coordinates are not established after you change the E-Gear ratio (P1.044 and P1.045).