Delta Electronics — 12.2 Causes and corrective actions

ASDA-B3 Troubleshooting 12 12-41 AL235 Position counter overflow warning Checking method and corrective action 4. Established the absolute origin coordinates, but the procedure is incomplete. 5. When AL060 and AL062 occur, use the scope to check if the feedback position has overflowed. And check whether the above situations have occurred, then establish the absolute origin coordinates. How to clear the alarm? Incremental system: perform homing procedure. Absolute system: establish the absolute origin coordinates. AL237 Indexing coordinate is undefined Trigger condition and cause You used the indexing function without firstly defining the starting point of the indexing coordinate.

Checking method and corrective action Perform the homing procedure before using the indexing function to avoid triggering this alarm. How to clear the alarm? DI.ARST AL245 PR positioning timeout Trigger condition and cause Condition: PR positioning function is triggered. Cause: the time for executing positioning is too long. Checking method and corrective action Check if the conditions for completing the PR commands are not set or triggered, causing the PR command incomplete. How to clear the alarm? DI.ARST or cycle power on the servo drive. AL249 PR number exceeds the range Trigger condition and cause Condition: the triggered PR path number exceeds the upper limit. Cause:

the triggered PR path number exceeds 99. Checking method and corrective action 1. Check if the PR command jumps to a path exceeding the range. 2. Check if the PR command format is correct. How to clear the alarm? DI.ARST or cycle power on the servo drive.