Delta Electronics — 12.2 Causes and corrective actions

ASDA-B3 Troubleshooting AL401 NMT reset command is received when servo is on Trigger condition and cause NMT reset command is received when the servo is on. 12 Checking method and corrective action Check if the NMT reset command is received when the servo is on. Use NMT: reset node or 0x6040 fault reset. How to clear the alarm? DI.ARST 12-47 AL404 Value of PR special filter setting is too high Trigger condition and cause Condition: the value of the PR special filter (P1.022) is set too high so that the following error of internal position exceeds the range. Cause: following error of internal position exceeds the allowable range.

Checking method and corrective action Check the setting of P1.022. If the value is set too high, the following error exceeds the allowable range faster. Re-adjust the value of P1.022. How to clear the alarm? DI.ARST AL500 STO function is enabled Trigger condition and cause Safe torque off function (STO) is enabled. Checking method and corrective action Safe torque off function (STO) is enabled. Check why it is enabled. How to clear the alarm? 1. Reset by using DI.ARST, 0x6040 fault reset, or setting P0.001 to 0. 2. If not using the STO function, plug the short circuit terminal into CN10 or wire to short-circuit the block. Follow the instructions in Chapter 3 for STO wiring.

AL501 STO A lost (signal loss or signal error) _ Trigger condition and cause Loss of STO A signal or STO A and STO B signals are not synchronized for more _ _ _ than 1 second. Checking method and corrective action Make sure the wiring of STO A is correct. _ How to clear the alarm? Cycle power on the servo drive.