Cummins — 4021330

C8.3 Industrial Battery Cables and Connections Section 4 - Maintenance Procedures at 75 Hours, or 3 Months Page 4-5 Use a hydrometer to measure the specific gravity of each cell. NOTE: If the specific gravity of any cell is below 1.200, the battery must be charged. NOTE: Do not attempt to check the specific gravity of a battery immediately after adding water. If it is necessary to add water to allow use of the hydrometer, charge the battery several minutes at a high rate to mix the electrolyte. Battery Cables and Connections Initial Check There are two possible heavy-duty battery connections: Battery terminal and clamp (1) Threaded battery terminal and nut (2).

Batteries can emit explosive gases. To reduce the possibility of personal injury, always ventilate the compartment before servicing the batteries. To reduce the possibility of arcing, remove the negative (-) battery cable first and attach the negative (-) battery cable last. WARNING Remove and inspect the battery cables and connections for cracks or corrosion. Replace broken terminals, connectors, or cables. If the connections are corroded, use a battery brush or wire brush to clean the connections until shiny. Make sure all debris is removed from the connecting surfaces.