2.51 VENTING AND LEAK CHECKING PROCEDURES FOR NATURAL GAS ENGINE (LOW PRESSURE SYSTEM) 2. Disconnect the batteries using switch(s) in the battery compartment or by disconnecting the battery ground cable. 3. Open fitting (before and after genset shutoff valve) to assure all pressure has been relieved in the natural gas fuel line. 4. Check all connections that were loosened for leaks after installation, service and troubleshooting are complete. 2.51.3 Leak Checking the Natural Gas Fuel System Use the following steps to check for leaks: 1. Open manual shutoff valve. 2. Start engine and run with no electrical load on generator. 3.

Spray soapy water or commercially available leak checking solutions on connections. Bubbles will form if there is a leak. 4. Repair any leak by: [a] Shut down the engine and close the manual shut off valve. [b] Tighten connection using the fitting technique of the manufacturer. NOTE: Vent fuel lines before replacing leaking components; refer to section 2.51.1 and refer to section 2.51.2. This will prevent a discharge of gas. [c] Replace leaking component. [d] Replace the pipe-threaded connector with a new one if the leak is a pipe thread connection. Use anaerobic sealant with Teflon (such as SWAK®) applied to the threads. 5. Re-check connection with procedure in step 1 thru step 3. 6.

Use a combustible gas detector to check for presence of natural gas. If natural gas is detected, continue looking for leaks until the locations of all the leaks are determined. 7. Repair the leak using the procedure in step 4. (Rev. 2005) All information subject to change without notice. 2-256 6SE483 0507 Copyright © 2005 DETROIT DIESEL CORPORATION