Removal and Installation of N-2001 LP Regulator/Converter Follow the procedures below for removal and reinstallation of the N-2001 regulator. N-2001 Removal Steps Refer to Figure 29. 1. Close the liquid outlet valve in the forklift cylinder or fuel storage container. 2. Purge the system of fuel by starting the engine and running until all trapped fuel in the system is exhausted and the engine shuts down. 3. Remove the fuel inlet line (1) from the lock-off, the vacuum lines (2) the regulator and disconnect the lock-off connector (3). 4. Remove the two rear-mounting bolts that hold the regulator to the support bracket. This will permit easier access to the remaining hose clamps. 5.
Remove the two cooling lines (4) from the regulator. NOTE: It will be necessary to either drain the coolant system or clamp off the coolant lines as close to the regulator as possible to avoid a coolant spill when these lines are disconnected. 6. Remove the fuel vapor outlet hose (5) from the regulator. Figure 29. N-2001 Regulator in Non-Certified System N-2001 Installation Steps Refer to Figure 29. 1. Install the fuel vapor outlet hose (5) onto the regulator. 2. Install the two cooling lines (4) onto the regulator. 3. Install the two rear-mounting bolts that hold the regulator to the support bracket. Use a torque wrench and tighten each bolt to 50-60 lbf-in (5.65- 6.78 N-m) 4.
Install the fuel inlet line (1) onto the lock-off, the vacuum line (2) onto the regulator and connect the lock-off connector (3). 5. Open the liquid outlet valve in the forklift cylinder or fuel storage container. G643(E) Service Manual Chapter 6. LPG FUEL DELIVERY SYSTEM 211