2-37 Point Operation [POINT 1] Inspection: Inspect the magnetic switch contact continuity. Inspection: Inspect the magnetic switch coil continuity Inspection: Inspect the thermal relay contact continuity. Note: Do not adjust the thermal relay operating current. If the thermal relay is operated to stop charging while the charger is in use, always check the cause of thermal relay operation, and reset the thermal relay after taking the remedial action. Push the reset lever lightly to reset the thermal relay. Inspection: Inspect the transformer insulation resistance.
Circuit tester range Ω × 1 Measurement terminals T−W, S−V, R−U Switch Msch ON 0 Ω Msch OFF ∞ Ω Resistance between A1 and A2 Circuit tester range See the Service Standards list. Ω × 1 Circuit tester range Ω × 1 Measurement terminals 95−96 Switch Not operated 0 Ω Operated state ∞ Ω Measurement terminals Between each coil and frame Standard value 0.2 MΩ or more