Encoder diagnostics | Diagnostics for encoders with 1 V PP /11 µA PP /1 V PP + Z1 interface 8 Resetting the count value The count value counts the signal periods of the incremental signals of the connected encoder. The count value is always an incremental value. The Reset the count value with the reference mark: parameter provides the following options: Selection Description Off The count value counts the signal periods without any other starting conditions. If this option is selected, you can set the Set the count value: parameter to On and enter a starting value in the Count value [steps] field.
After tapping Back, the count value is set to the starting value entered and the product starts counting. Once The count value is set to "0" and counting starts with the detection of the reference mark. When the count value is detected, the parameter is set to Off again. With each The count value is set to "0" and counting starts with the detection of the reference mark. When the next reference mark is detected, the count value display freezes for approx. 0.5 s. This enables you to check the number of signal periods between reference marks for distance-coded encoders, for example.
c-Coded The count value is set to "0" and is then changed to the correspond- ing count value after the coding of the reference marks has been detected. When the count value is detected, the parameter is set to Off again. Defining the count values The Set the count value: parameter contains the starting value from which the product starts counting. The following instruction describes the entry of the count value: Tap More The More menu is opened Tap Counter The Display options for count value screen is opened Tap the Off option of the Reset the count value with the reference mark: parameter Tap the On option of the Set the count value:
parameter Count value [steps] is displayed Tap Count value [steps] The product's on-screen keyboard is opened Enter the desired starting value Tap OK Tap Back The changed settings take effect The Display options for count value screen is closed 92 HEIDENHAIN | PWT 100, PWT 101 | Operating Instructions | 07/2024