Case IH AFX8010 — CLEANING Primary cleaning

CROP PROCESSING - CLEANING Primary cleaning A. If continuity is found, continue with Step 12 . B. If no continuity is found, erase the fault codes and continue operation. 12. Disconnect connector X005 . Use a multimeter to check for continuity between connector X005 pin 15 and chassis ground. A. If continuity is found, continue with Step 13 . B. If no continuity is found, the short to ground is in the cab main (CM) harness between connector X005 pin 15 and the Upper/lower sieve relay K18 pin 3 on the fuse panel wire 786 red. Locate the short and repair. 13. Disconnect connector X219 . Use a multimeter to check for continuity between connector X219 pin 1 and chassis ground. A.

If continuity is found the short to ground is in the expansion (EX) harness between connector X219 pin 1 and connector X013 pin J2-21 wire 786 red. Locate the short and repair. B. If no continuity is found, the short to ground is in the main frame (MF) harness between connector X005 pin 15 and connector X219 pin 1 wire 786 red. Locate the short and repair. 14. Fault codes indicate circuit fault due to open circuit condition. Disconnect the lower sieve motor connector X228 . Measure the resistance of the motor between terminals D and E. The correct resistance is 3 - 12 ohms . A. The resistance is infinite, indicating an open condition in the motor. Replace the lower sieve motor. B.

The resistance is in specification. Continue with Step 15 . 15. Replace the Upper/lower sieve relay K18 on the fuse panel with a known good relay, and retest the upper sieve circuit function. A. If the lower sieve circuit now functions properly, the relay was faulty, and was not providing continuity between terminals 3 & 5 when energized. Replace the relay. B. If the lower sieve circuit still does not work, continue with Step 16 . 16. Ensure that the batteries are connected, and that fuse F27 is good. Use the multimeter to check for continuity between connector X228 pin E and chassis ground. A. If continuity is found, continue with Step 19 . B.

If no continuity is found, continue with Step 17 . NOTE: The CCM module connects both sides of the circuit to ground when in neutral to "lock" the motor in position, irregardless of key switch position, as long as it receives power through fuse F27. This ground path may be used to test for an open circuit condition. 17. Disconnect connector X072 . Use a multimeter to check for continuity between connector X072 pin P and chassis ground. A. If continuity is found, the open circuit is in the lower frame rear (LR) harness between connector X072 pin P and connector X228 pin E wire 789 gray. Locate the open and repair. B. If no continuity is found, continue with Step 18 . 18.

Disconnect connector X025 . Use a multimeter to check for continuity between connector X025 pin 14 and chassis ground. A. If continuity is found, the open circuit is in the straw hood front (SW) harness between connector X025 pin 14 and connector X072 pin P wire 789 gray or 785 gray. Locate the open and repair. B. If no continuity is found, the open circuit is in the expansion (EX) harness between connector X025 pin 14 and connector X013 pin J2-1 on wire 785 gray. Locate the open and repair. 19. Remove the Upper/lower sieve relay K18 on the fuse panel, and install a jumper wire between terminals 3 & 5. Use a multimeter to check for continuity between connector X228 pin D and chassis ground.

A. If no continuity is found, continue with Step 20 . 9717 1 27/05/2004 K.62.B / 100