COOLING SYSTEM, AIR-TO-AIR CHARGE COOLING Basic engine coolant capacity is found on www.detroitdiesel.com, if you do not have access to www.detroitdiesel.com contact your Distributor. 8.7.5 DRAWDOWN CAPACITY Drawdown capacity is the amount of coolant which can be removed from the system before the coolant pump begins to cavitate. The drawdown capacity for DD Platform engines is 10% of the total cooling capacity. System design must permit reasonable loss of coolant from the hot full level before aeration of the coolant begins. Additional coolant capacity may be necessary if aeration begins before this point. Perform drawdown tests at the maximum tilt angle.
8.7.6 CORE CONSTRUCTION Tube and plate fin design is preferred because of lower restriction to both air and coolant flow. Tube and plate fin designs are easier to clean than louvered serpentine types and generally of more rugged construction making it more suitable to operate in the diesel engine environment. 8.7.7 WATER PUMP INLET PRESSURE/MAXIMUM STATIC HEAD When the engine is operating at maximum rated engine speed, fill cap removed, and thermostat fully opened, the water pump inlet pressure must not be lower than atmospheric pressure (suction) with a rapid warm-up cooling system These requirements must be met to minimize water pump cavitation and corresponding loss in coolant flow.
Keep restrictions to the water pump inlet such as radiator cores, heat exchanger, auxiliary coolers and the associated plumbing to a minimum. The maximum static head allowed on DD Platform engines is 145 kPa (21 psi). and the pressure relief valve or cap must be sized so the limit is not exceeded. Consider a non-pressurized vented cap system for radiators mounted 312 m (5 ft.) and higher above the engine. This ensures that the limit is not exceeded. 8.7.8 COOLANT FLOW RATE/EXTERNAL PRESSURE DROP The coolant flow rate through the engine and radiator must be within 90% of the rated flow .found on www.detroitdiesel.com, if you do not have access to www.detroitdiesel.com contact your Distributor.
Ensure that the flow is maintained when coolant is shunted away from the engine or radiator to supply cab heaters, air compressors, auxiliary coolers, wet exhaust systems, etc. External pressure drop is defined as the sum of all components in the system. For example, a radiator with a 21 kPa (3 psi) restriction plus a heat exchanger, with a 14 kPa (2 psi) restriction mounted between the water pump and oil cooler gives a total pressure drop of 34 kPa (5 psi). This is within the typical DD Platform engine maximum allowable value. See www.detroitdiesel.com for current data. 8-16 All information subject to change without notice. DDC-SVC-MAN-0073 Copyright © 2009 DETROIT DIESEL CORPORATION