COOLING SYSTEM, AIR-TO-AIR CHARGE COOLING Figure 8-17 Blower vs. Suction Fans 8.13.1.1 Fan Performance Fan curve air flow (m 3 /min. [ft. 3 /min.]) is a theoretical output value which is seldom achieved. This value can be approached with a well formed, tight fitting shroud and proper fan positioning (fan tip clearances of 1/16 in. [1.59 mm] or less). Consult the fan supplier on how to determine what the realistic fan air flow delivery will be on the installation. Select a fan/core match with sufficient reserve cooling capacity to allow for some degradation. This degradation occurs as the unit gets older and there is fouling from airborne debris.
These conditions cause higher air restriction and/or lower heat transfer capability. This is especially true for applications such as agriculture, earth moving, or mining. Fin density should be as low as practical to keep air flow high, minimize plugging, and permit easier cleaning. NOTE: Fin density in excess of 10 fins per inch should be reviewed with Detroit Diesel Application Engineering. 8-30 All information subject to change without notice. DDC-SVC-MAN-0073 Copyright © 2009 DETROIT DIESEL CORPORATION