DD PLATFORM APPLICATION AND INSTALLATION MANUAL Adequate expansion and deaeration volume as well as sufficient coolant volume so the system will operate satisfactorily with partial loss of coolant Impose a positive head on the water pump Prevent coolant flow through the radiator core during closed thermostat operation Prevent introduction of air into the cooling system during maximum tilt or angle operation 8.14.1.3 Remote Mounted Radiators/Heat Exchanger Consult an authorized distributor, radiator supplier, or DDC Application Engineering when remote (i.e. non engine driven fans) mounted radiators/heat exchangers are being considered as many variables must be considered for each application.
The requirements that must be met for remote mount are: Standard DDC installation and test requirements including restriction to flow and coolant flow rate Maximum allowable static head pressure is 32 ft. of water column with a pressure cap, 50 ft. of water column with an open system Installations where flow rate restrictions cannot be met may require using an inline pump 8.14.1.4 Integral Top Tank The following top tank component guidelines are provided to assist in the design of a new tank, to critique existing tanks, and to troubleshoot problem cooling systems. All information subject to change without notice. 8-37 DDC-SVC-MAN-0073 Copyright © 2009 DETROIT DIESEL CORPORATION