DD PLATFORM APPLICATION AND INSTALLATION MANUAL Figure 8-22 Remote Surge Tank Design for Rapid Warm-up Cooling System Table 8-5 Component Design and Location Guidelines for the Remote Top Tank All information subject to change without notice. 8-41 DDC-SVC-MAN-0073 Copyright © 2009 DETROIT DIESEL CORPORATION Component and Location Guidelines Radiator Inlet Tank Must be large enough so air can be separated from the coolant. The deaeration line from the radiator inlet tank to the remote/top tank must be at the highest point of each and generally as far away from the inlet as practical. Location Locate tank as high as practical.
The bottom of the tank should be above the rest of the cooling system. This will prevent coolant level equalization problems. Generally, low mounted tanks make filling the system more difficult, especially near the end of the fill, because of small head differential. Also, equalization of the coolant level occurs during engine stop or low speed operation.