MAN — MAN DD13 DD15 Engine Application Installation Manual

COOLING SYSTEM, AIR-TO-AIR CHARGE COOLING Table 8-4 Top Tank Component Guidelines— Fill Neck, Fill Neck Vent Hole, and Coolant Level Sensor General guidelines for top tank design, critique, or troubleshooting are: Increasing top tank depth permits maximum usage of coolant volume and reduces tilt operation problems. Consider hose fitting inside diameters when determining vent and fill line inside diameter requirements. Low fill line flow velocity (large inside diameter line) will generally improve drawdown capacity and maintain higher pressure on the water pump.

Oversized and/or excessive number of deaeration line(s) and standpipe(s) can result in poor deaeration and drawdown capabilities and increases coolant flow bypassing the radiator core. Undersizing deaeration line(s) and standpipe(s) may not provide adequate deaeration and they can become plugged easier. Make observations of top tank agitation, deaeration and fill line(s), flow direction, and velocity during both open and closed thermostat operations (throughout engine speed range), to determine satisfactory system design. The observations are especially helpful during fill and drawdown evaluation tests.

A sight glass in the radiator top tank to determine proper coolant level will eliminate unnecessary removal of the radiator cap. 8.14.1.5 Remote Tank The design of the remote tank must provide the same features as the integral top tank design. The guidelines for the radiator inlet tank are listed in the following table. 8-40 All information subject to change without notice.

DDC-SVC-MAN-0073 Copyright © 2009 DETROIT DIESEL CORPORATION Component Guidelines Fill Neck Select the fill neck size capable of accepting highest rated pressure cap required for application The fill neck cap must provide safe release of system pressure upon removal of the cap when a separate pressure relief valve is used. Locate the fill neck at the top center of the top tank. This will ensure a complete fill if unit is in a tilted position. Fill Neck Vent Hole A 1/8 in. (3.18 mm) vent hole located at the top of the fill neck extension is required for venting air and preventing coolant loss. Low Coolant Level Sensor Location must be above the satisfactory drawdown coolant level.

This is generally a height representing 98% of the drawdown quantity. Coolant flow and/or splash from deaeration line and standpipe(s) must not contact sensor. A shroud around the sensor may be beneficial. Locating the sensor in the middle of the tank will minimize tilt operation sensitivity.