AUXILIARY AIR SYSTEMS 15.1 AIR START The system must provide an engine cranking speed above 100 rpm for a minimum period of 10 seconds at 44°C (40°F), without recharging the air tank. A 15 second or longer cranking period is recommended for optimum starting. Engine cranking speed above 250 rpm is not necessary. Energy spent above 250 rpm would be better used to extend the cranking period. Starting aids may be required if the engine must be started in an ambient below 44°C (40°F). 15.1.1 SYSTEM RECOMMENDATIONS The following sections list the system recommendations for air tanks, the air control system, air starters, and hoses.

15.1.1.1 Air Tanks The following is a list of system recommendations for air tanks: Air tanks should meet ASME pressure vessel specifications. Include a safety valve and pressure gage. An air drain cock should be provided in the lowest part of the air tank to drain condensation. Use of an air dryer is recommended at the compressor outlet to minimize condensation in the air tank. There should be zero leak down of air tank pressure when the equipment is idle. A check valve at the air tank inlet is recommended. Connections to the air tank should be such that there is no trapped moisture in the system. Typical minimum air tank size for the DD Platform is 65 gallons. NOTE:

The minimum air tank size of 65 gallons is not a recommended tank size. Larger tanks may be required for a given application, starter type, or starting system. Contact the air starter manufacturer for proper tank size. 15.1.1.2 Air Control System The system should disengage the starter and shut off the air supply to the starter the instant the engine starts. This will conserve air pressure for the next start attempt, if required. Use a 3 to 5 psi fuel pressure switch to trigger starter disengagement. Sensing lube oil pressure is not recommended due to slow response time. The system should have a lockout to prevent an attempt to engage the starter into a running engine.

A 3 to 5 psi fuel pressure switch will serve to prevent starter engagement while the engine is running. 15-2 All information subject to change without notice. DDC-SVC-MAN-0073 Copyright © 2009 DETROIT DIESEL CORPORATION