Service Manual for WD10 Diesel Engine b) Low charging voltage 126 b. Check whether generator output end B+ to ground voltage is about 24V (battery voltage). a. If B+ terminal to ground voltage is zero, then check generator to battery positive and negative circuits for breakover. b. If B+ terminal to ground voltage is obviously lower than battery voltage, then check whether generator to battery positive and negative circuits are loose or the battery is damaged. Recommended detection method: Connect a 2W indicator lamp to generator B+ terminal and exciting D+/L terminal, observe working condition of the indicator. Troubleshooting:

 The brightness of indicator lamp is normal, and it goes out automatically after engine is started, generator output voltage is 27~28.5V; it means the exciting circuit has problem and needs to be repaired.  The brightness of indicator lamp is normal, but it doesn’t go out after engine is started, generator output voltage is 27~28.5V; it means generator regulator has problem and needs to be checked.  The brightness of indicator lamp is normal, but it doesn’t go out after engine is started, generator output voltage is battery voltage; it means there is fault in generator regulator, rectifier bridge, stator or inner connectors, and needs to be repaired or replaced.