Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 5 – Maintenance Procedures Page 5 - 5 CFP83 Series Press down, unscrew and remove the pressure cap (Cummins Fire Power Part No. 11407). NOTE : Coolant level should be at the bottom of the fill neck. It must be above the raw water tubes. Check coolant level. NOTE : Make up coolant added to the engine must be mixed with the correct proportions of antifreeze, supplemental coolant additive and water to avoid engine damage. Coolant specifications can be found in Coolant Recommendations and Specifications in Section 7. If required, prepare a coolant solution. Fill the cooling system with coolant to the bottom of the fill neck in the coolant heat exchanger.

When done, press down and screw in the pressure cap (Cummins Fire Power Part No. 11407). Procedure 3 Check Crankcase Breather Tube Inspect the breather tube for sludge, debris, or ice in the tube. If the breather tube is obstructed or blocked, clean it. Inspect the tube more frequently in icy conditions. Drawing No. 9777, Section 5, Rev. 02-07