Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 5 – Maintenance Procedures Page 5 - 13 CFP83 Series Check that both battery voltmeters indicate 12 VDC standard (24 VDC optional) depending upon the application. Check that the inlet air restriction indicator has not popped-up. Red plunger would be popped as shown. Check that the Fuel Injection Failure (F.I.F.) light is not turned on. End Test Run Select the AUTO position on the AUTO/MANUAL Switch. Drawing No. 9777, Section 5, Rev. 02-07