Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 5 - 16 Section 5 – Maintenance Procedures CFP83 Series Supplemental Coolant Additive(SCA) Check the SCA concentration level: ~At least twice a year ~At every subsequent oil drain interval if the concentration is above 3 units ~Whenever coolant is added to the cooling system between filter changes. Use Fleetguard® coolant test kit, Part No. CC2602, to check the SCA concentration level. Instructions are included with the test kit. Refer to Coolant Recommendations and Specifications in Maintenance Specifications (Section V) for the correct SCA and antifreeze level. Antifreeze CAUTION Over concentration of antifreeze or use of high- silicate antifreeze can damage the engine.

Check the antifreeze concentration. Use a mixture of 50-percent water and 50-percent ethylene glycol-base antifreeze to protect the engine to -37°C [-34°F] year-around. Antifreeze is essential in any climate. It broadens the operating temperature range by lowering the coolant freezing point and raising its boiling point. The corrosion inhibitors also protect the cooling system components from corrosion and provide longer component life. Procedure 20 Check Air Cleaner Service Indicator CAUTION Never operate the engine without an air cleaner. Unfiltered foreign objects could cause engine damage.

Turbocharged engines must be operated at rated RPM and full load to check maximum intake air restriction. Replace the air cleaner element when the restriction reaches the maximum allowable limit, or clean according to the manufacturer's recommendations. Maximum intake air restriction is 762 mm H2O [30.0 in H2O] for turbocharged engines. Drawing No. 9777, Section 5, Rev. 02-07