Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 5 - 26 Section 5 – Maintenance Procedures CFP83 Series WARNING Wear appropriate eye and face protection when using compressed air. Flying debris and dirt can cause personal injury. After the charge air cooler has been thoroughly cleaned of all oil and debris with solvent, wash the charge air cooler internally with hot, soapy water to remove the remaining solvent. Rinse thoroughly with clean water. Blow compressed air into the charge air cooler in the opposite direction of normal airflow until the charge air cooler is dry internally. Refer to Section 4 for installation procedures.

Procedure 26 Lubrication of Output Shafts It is recommended that proper lubrication to drive shafts and output shafts is to be completed on a regular schedule. Grease zerk fittings as shown. See Section 10 for grease specifications and lubricating oil recommendations. Drawing No. 9777, Section 5, Rev. 02-07