Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 5 - 28 Section 5 – Maintenance Procedures CFP83 Series Check for damaged hoses and loose or damaged hose clamps. Replace as required. Check the heat exchanger for leaks, damage, and buildup of dirt. Clean and repair as required. Flush CAUTION During filling, air must be vented from the engine coolant passages. The air vents through the “jiggle pin” openings to the top heat exchanger hose and out the fill opening. Additional venting is provided for engines equipped with an after cooler. Open the petcock during filling. NOTE : Adequate venting is provided for a fill rate of 10 liters/minute [2.6 gal/min]. Drawing No. 9777, Section 5, Rev.

02-07 valve in the will be Drain the cooling system by opening the drain valve on the heat exchanger and removing the plug in the bottom of the water inlet. A drain pan with a capacity of 20 liters [5 gal] will be adequate in most applications. valve in the will be